Skip to main navigation.

Rate 901

RATE 901

LARGE THREE-PHASE PRIMARY METERED SERVICE ABOVE 750 KVA

AVAILABILITY

Available to any member where transformer capacity is 750 KVA or greater and is located in the REMC’s service area and located adjacent to an electric transmission or distribution line of the REMC that is adequate and suitable for supplying required service. Not applicable as standby service.

 

CHARACTER OF SERVICE

Multi-phase, sixty (60) Hertz at the approximate standby voltages; 277/480 volts 4-wire; 7,200/12,470 volts; or other voltages as may be mutually agreeable.

 

MONTHLY RATE

  • Consumer Charge - $192.46 per month
  • Demand Charge applicable for all kW’s - $17.19 per kW
  • Energy Charge all kWh - $.0484 per kWh

 

DETERMINATION OF BILLING DEMAND

The billing demand shall be the maximum kilowatt load used by the member for any period of fifteen (15) consecutive minutes during the month for which the billing is rendered as indicated on record by a maximum load meter installed by the REMC. An adjustment for power factor as provided below shall be provided.

 

POWER FACTOR

The consumer agrees to maintain unity power factor as nearly as practical. The REMC reserves the right to measure such power factor at any time. Should such measurements indicate that the power factor is less than  97 percent, the demand for billing purposes will be adjusted for average monthly lagging power factor by multiplying the demand as indicated or recorded on the demand meter by  97 percent and divided by the percent power factor.

 

MINIMUM MONTHLY CHARGE

The minimum monthly charge shall be the highest of the following:

  1. The specified contract amount, or 
  2. Charges as outlined under Determination of Billing demand plus metered energy.

 

METERING

The metering will be at the REMC’s primary service (7.2/12.47 kV).

 

The customer shall own, operate, and maintain all facilities on customer side of meter.

 

CONDITION OF SERVICE

  1. Service shall be provided based upon the REMC’s rules and regulations.
  2. The member shall be required to enter into a written agreement stating the character of load, minimum contract period, minimum monthly charge and other charges, if any.
  3. All energy shall be supplied to one location through one set of meters.
  4. The REMC may require relay and/or protective equipment and approve settings for protection of REMC’s system.
  5. REMC reserves the right to set maximum starting current values of motors over 50 horsepower.
  6. The REMC may require corrective measures or devices for any motor or apparatus, which in the opinion of the REMC will cause voltage fluctuation, harmonics or other power conditions. Unless otherwise permitted, the maximum primary voltage fluctuation is 3 percent or IEEE Standard 519.
  7. The member shall be responsible for installing under voltage or loss of phase relays for the protection of the member’s equipment.
  8. All wiring, pole lines, wire and other electrical equipment beyond the point where the service wires of the member connect to the service wires of the REMC shall be considered the distribution system of the member and shall be furnished and maintained by the member, except that metering equipment shall be furnished and maintained by the REMC.

   

RATE ADJUSTMENT

The above rates are subject to the following charges and conditions:

POWER AND FUEL COST ADJUSTMENT (REFER TO APPENDIX A)
TERMS OF PAYMENT (REFER TO APPENDIX B)
NONRECURRING CHARGES (REFER TO APPENDIX B)
CUSTOMER DEPOSITS (REFER TO APPENDIX C)
Powered by Touchstone Energy Cooperatives Logo